Lead supply pipe leak by a front gate found in Dinmore
The meter kept turning with the inside stopcock off. Listening along the outside supply gave a high reading by the boundary wall and front gate, tracer gas gave a high reading at the same spot, and the damaged lead pipe was repaired there.

Signs of the leak in Dinmore
Water was flowing through the meter even with the inside stopcock turned off. The combi boiler had needed no top-ups. The outside supply failed a 3.5 bar test within five minutes, while the inside pipework held 3.5 bar for twenty minutes.
How acoustic equipment found it
The engineer listened along the route of the outside supply pipe and recorded a high reading next to the boundary wall and front gate. Tracer gas then gave a high reading at the same place, so the dig was made there with both methods agreeing.
The investigation, step by step
- 01Flow test at the meter showed water passing with the inside stopcock off.
- 02Pressure tested the outside supply at 3.5 bar; it failed within five minutes.
- 03Pressure tested the inside pipework at 3.5 bar; it held for twenty minutes.
- 04Listened along the outside supply route and got a high reading by the boundary wall and front gate.
- 05Put tracer gas into the pipe and got a high reading at the same spot.
- 06Dug at that point and exposed the damaged 1/2 inch lead supply pipe.
- 07Repaired it with two transition couplings and a short length of 20mm MDPE pipe.
- 08Retested: no flow at the meter, and the outside supply held 3.5 bar for twenty minutes.



What was found
- Found
- A damaged section of 1/2 inch lead supply pipe in the ground next to the boundary wall and front gate.
- Repair
- The damaged section was cut out and bridged with two transition couplings and a short length of 20mm MDPE pipe. Afterwards the meter showed no flow and the outside supply held 3.5 bar for twenty minutes.
- Recommended afterwards
- Relay the whole lead supply pipe in a modern material when the chance arises.
- Worth knowing
- The rest of the lead supply pipe is still in the ground either side of the repair.